  • The Circutor EC72 F III+N 500V (code M10728) is a panel-mount analog voltmeter with an integrated phase selector switch for AC voltage measurement on three-phase 4-wire systems. It measures phase-to-neutral voltages up to 500 V at Class 1.5 accuracy and fits a standard 72 x 72 mm panel cutout.

    Technical specifications:

    • Model: EC72 F III+N 500V
    • Circutor code: M10728
    • EAN: 8433059005245
    • System: Three-phase 4 wire
    • Measurement range: 500 V
    • Accuracy class: 1.5 (1.5% FE)
    • Scale: 90, pointer position P1
    • Panel module size: 72 x 72 mm
    • Overall dimensions (W x H x D): 72 x 72 x 49.2 mm
    • Weight: 0.166 kg
    • Mounting: Panel (flush)
    • Front protection: IP 52
    • Terminal protection: IP 00
    • Working temperature: +10 to +30 C
    • Storage temperature: -25 to +40 C
    • Frequency range: 20 to 100 Hz
    • Measurement circuit consumption: 1 to 4 VA
    • Maximum continuous voltage: 1.5 x Vn continuous; 2 x Vn for 5 seconds
    • Insulation voltage: 2 kV at 50 Hz for 1 minute (between mechanism and case)
    • Maximum installation altitude: 2000 m
    • Standards: BS 89, UNE-EN 60051, IEC 144, DIN 43780, IEC 51, UNE 21318
    • Certifications: CE

    Features and benefits:

    • Integrated phase selector switch lets a single instrument display each phase-to-neutral voltage in a three-phase 4-wire network, removing the need for three separate meters.
    • IP 52 front protection resists dust ingress and light water splashes, making it suitable for industrial control panel environments.
    • Class 1.5 accuracy with compliance to IEC 51, UNE-EN 60051, and DIN 43780 ensures reliable, standards-verified voltage readings.
    • Frequency operating range of 20 to 100 Hz accommodates both fixed-frequency mains supplies and variable-frequency drive output circuits.
    • Standard 72 x 72 mm flush-mount format drops directly into conventional switchboard and control panel cutouts without adapters.

    Applications:

    • Phase voltage monitoring in industrial switchboards and motor control centres on three-phase 4-wire low-voltage networks.
    • Power distribution panels in commercial and industrial buildings where individual phase voltages must be verified at a single instrument.
    • Electrical test benches and laboratory panels requiring a CE-certified, panel-mount AC voltmeter meeting international standards.
    • Control cabinets serving machinery powered by variable-frequency drives operating across a broad 20 to 100 Hz frequency range.

    Also known as: Circutor EC72 F III+N 500V, EC72 F III+N 500V M10728, Circutor M10728, three-phase panel voltmeter with phase switch, 500 V analog voltmeter.

    Add a Review

    Your email address will not be published. Required fields are marked *