Schneider LRD08 TeSys Deca Thermal Overload Relay 2.5-4A

$21.78 $17.42

  • Shipping Icon
    Free
    Shipping
  • Shipping Icon
    Safe
    Payment
  • Shipping Icon
    Best
    Services
Categories :
  • Electrical
  • The Schneider Electric LRD08 is a TeSys LRD differential thermal overload relay with a 2.5-4 A adjustment range, designed for motor protection in industrial applications. It provides Class 10A tripping performance per IEC 60947-4-1 and mounts directly below compatible TeSys D contactors including LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, and LC1D38.

    Technical specifications:

    • Commercial reference: LRD08
    • Manufacturer: Schneider Electric
    • EAN: 3389110346787
    • Series / range: TeSys Deca
    • Product type: Differential thermal overload relay
    • Application: Motor protection
    • Thermal overload adjustment: 2.5-4 A
    • Tripping class: Class 10A per IEC 60947-4-1
    • Tripping threshold: 1.14 +/- 0.06 Ir per IEC 60947-4-1
    • Phase loss sensitivity: Trips at 130% of Ir in two phases, last phase at 0
    • Network type: AC / DC
    • Network frequency: 0-400 Hz
    • Rated voltage [Ue]: 690 V AC per IEC 60947-4-1
    • Rated insulation voltage [Ui]: 690 V per IEC 60947-4-1; 600 V per UL and CSA
    • Rated impulse withstand voltage [Uimp]: 6 kV
    • Auxiliary contact: 1 NO + 1 NC
    • Thermal current in air [Ith]: 5 A (control circuit)
    • Mounting: Below contactor; plate or DIN rail with accessories
    • Connection type: Screw terminal blocks
    • Tightening torque: 1.7 N.m (power and control circuits)
    • Dimensions (W x H x D): 45 x 66 x 70 mm
    • Weight: 0.124 kg
    • IP protection: IP20 per IEC 60529
    • Operating temperature: -20-60C
    • Storage temperature: -60-70C
    • Standards: EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, GB/T 14048.4, EN 50495
    • Certifications: IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, ATEX, UKCA

    Features and benefits:

    • Mounts directly below TeSys D contactors for compact, integrated motor starter assemblies
    • Built-in phase loss sensitivity detects single-phasing and trips at 130% of Ir
    • Temperature compensation across -20-60C maintains consistent tripping accuracy
    • Red stop and blue reset push buttons for straightforward manual control and reset
    • Broad global certification including ATEX, UKCA, DNV-GL, and LROS for marine and hazardous environments

    Applications:

    • Motor protection in industrial control and automation panels
    • Pump and conveyor motor starter assemblies
    • HVAC motor protection circuits
    • Machine tool and compressor motor control

    Compliant with EN/IEC 60947-4-1 and EN/IEC 60947-5-1. Part of the Schneider Electric TeSys Deca range.

    Also known as: Schneider LRD08, Schneider Electric LRD08, TeSys thermal overload relay 2.5-4A, motor protection relay LRD08.