Schneider LRD05 TeSys Deca Thermal Overload Relay 0.63-1A

$21.13 $16.90

  • Shipping Icon
    Free
    Shipping
  • Shipping Icon
    Safe
    Payment
  • Shipping Icon
    Best
    Services
Categories :
  • Electrical
  • The Schneider Electric LRD05 is a TeSys LRD thermal overload relay with a current setting range of 0.63-1 A, designed for motor protection in AC and DC networks. Part of the TeSys Deca range, it delivers tripping class 10A per IEC 60947-4-1 and mounts directly below LC1D-series contactors for a compact, integrated motor starter assembly.

    Technical specifications:

    • Commercial reference: LRD05
    • Manufacturer: Schneider Electric
    • EAN: 3389110346756
    • Series / range: TeSys LRD / TeSys Deca
    • Product type: Differential thermal overload relay
    • Relay application: Motor protection
    • Current setting range: 0.63-1 A
    • Tripping class: Class 10A per IEC 60947-4-1
    • Network type: AC / DC, 0-400 Hz
    • Rated insulation voltage [Ui]: 690 V (IEC 60947-4-1), 600 V (UL/CSA)
    • Rated impulse withstand voltage [Uimp]: 6 kV
    • Tripping threshold: 1.14 +/- 0.06 Ir per IEC 60947-4-1
    • Auxiliary contact: 1 NO + 1 NC
    • Compatible contactors: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38
    • Mounting: Below contactor, on panel or DIN rail (with separate accessories)
    • Connection: Screw terminal blocks; power circuit 1.5-10 mm, control circuit 1-2.5 mm
    • IP protection: IP20 per IEC 60529
    • Operating temperature: -20…60 C per IEC 60947-4-1
    • Storage temperature: -60…70 C
    • Dimensions (WxHxD): 45 x 66 x 70 mm
    • Weight: 0.124 kg

    Features and benefits:

    • Phase loss sensitivity: trips at 130% of Ir on two phases with the last phase at zero, guarding against single-phasing damage
    • Temperature compensation across the full -20…60 C operating range ensures accurate, consistent tripping
    • Integrated red stop button and blue reset button for convenient local manual control
    • Direct plug-in mounting below LC1D contactors eliminates additional wiring for a compact motor starter
    • Broad certification portfolio including ATEX INERIS, UKCA, and marine approvals (DNV-GL, BV, RINA, LROS) for demanding environments

    Applications:

    • Motor protection in industrial motor control centers and automation panels
    • Combined motor starters assembled with LC1D09 through LC1D38 contactors
    • Pump, fan, and compressor drive overload protection
    • Marine and hazardous area installations requiring DNV-GL, BV, or ATEX certification

    Compliant with EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and GB/T 14048.4. Part of the Schneider Electric TeSys Deca range.

    Also known as: Schneider LRD05, Schneider Electric LRD05, TeSys thermal relay, motor overload relay 1A.